Fallah Tafti M, Haji Beigi B, Mousavi Hosseini K, Karimi G. Evaluation of the physical structure and safety conditions of the blood transfusion center's electrification network using the energy tracking and Barrier analysis method. Sci J Iran Blood Transfus Organ 2023; 20 (4) :312-327
URL: http://bloodjournal.ir/article-1-1513-en.html
Abstract:   (780 Views)
Abstract
Background and Objectives
Constant control of electrical panels is effective in ensuring the safety of users. This study was conducted during the years 2022-2023 to evaluate their structure in blood transfusion centers by ETBA method.

Materials and Methods
In this descriptive-analytical study with the ETBA method, the performance and quality of the grounding system, capacitor bank, connections, the location of the panels, the arrangement structure of the components, and their cleanliness and safety in the centers of Kermanshah, Hamadan, Ilam, Sanandaj, Arak, Karaj, Semnan, Bandar Abbas, Sari and Yazd were investigated. The obtained information was analyzed statistically with SPSS 25 software.

Results
The results showed 74.3% electrical panels with unprincipled volume and distribution of connections, 72.4% due to the selection of inappropriate location and distance from tools and devices, deployment in users' traffic area without provision of fence and safety devices, 70.5% not equipped with warning devices, 43.3% non-standard arrangement, 51.4% insufficient cleaning, 66.3% not having an active earth connection, and 60.3% not having a capacitor bank did not have reliable electrical safety.

Conclusions 
Based on these results, the regular and continuous establishment and implementation of the medical equipment maintenance management system can be a fundamental and effective factor in identifying risks and the pertinent degree of risks and damages in the process of activity.

Full-Text [PDF 877 kb]   (400 Downloads) |   |   Full-Text (HTML)  (320 Views)  
Type of Study: Research | Subject: Biotechnology
Published: 2023/12/31

Add your comments about this article : Your username or Email:
CAPTCHA

Send email to the article author


Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.

© 2025 CC BY-NC 4.0 | Scientific Journal of Iran Blood Transfus Organ

Designed & Developed by : Yektaweb